@inproceedings{ed880787f3864377b48d9f735360e758,
title = "Implementation of Directional Incremental-Quantity Relay in Simulink",
abstract = "This paper elaborates the implementation of the time-domain directional TD32 protective function, introduced by SEL, in Matlab/Simulink. TD32 is a function of transmission line relay T401L made by SEL. We modeled TD23 based on the user manual of SEL T401L, and researchers who need to simulate this relay can use the model we made available on the IEEE DataPort. The algorithm of TD32 employs the theory of incremental quantities to identify the direction of a fault and find the fault type faster compared to the traditional frequency-domain directional algorithms. The solid performance of the implemented relay is verified by comparing its outputs with the recorded outputs of a T401L relay in response to a real-world fault.",
keywords = "Incremental quantities, TD32, directional relay, time-domain",
author = "Julio Rodriguez and Hamidi, {Reza Jalilzadeh}",
note = "Publisher Copyright: {\textcopyright} 2023 IEEE.; 2023 IEEE SoutheastCon, SoutheastCon 2023 ; Conference date: 01-04-2023 Through 16-04-2023",
year = "2023",
doi = "10.1109/SoutheastCon51012.2023.10114960",
language = "English",
series = "Conference Proceedings - IEEE SOUTHEASTCON",
publisher = "Institute of Electrical and Electronics Engineers Inc.",
pages = "11--16",
booktitle = "SoutheastCon 2023",
address = "United States",
}